Kyoritsu 4202 Earth Clamp Tester

Harga :
CALL
Merk :
Kyoritsu
Pengiriman :
3 hari sejak pembayaran
Lokasi :
Dilihat :
160 Kali
Update Terakhir :
15-12-2014 16:02

Detail Produk

 

Earth Clamp Tester

• Real time measurements can be transferred, shown and saved on Android device ( up to 100 measurements) 
• Saved data includes measurement, GPS location and date & time
Easy to check on map " When " and " Where " the measurement was made
• Comparator function on Android device informs when the measured value is lower/ higher than the preset value
4202
CE
Earth / Ground resistance and Leakage current measurement functions
• The earth resistance from 0.05 to 1200 © can be measured without the auxiliary earth spikes in multi-earthing systems
• True RMS leakage or phase current readings from 0.1mA to 30.0A provides vital additional information in earthing networks
• Filter function offers increased immunity to electrical noise and a Noise mark appears in excessively high noisy environments

Function Range Resolution Measuring Range Accuracy
Earth resistance
Auto range 20© 0.01© ( * ) 0.00~ 20.99© | ± 1.5% ± 0.05© 
200© 0.1© 16.0~ 99.9© | ± 2% ± 0.5© 
100.0~ 209.9© | ± 3% ± 2© 
1200© 1© 160~ 399© | ± 5% ± 5© 
400~ 599© | ± 10% ± 10© 
10© 600~ 1260© ---
AC current
( 50Hz/ 60Hz) 
Auto range 100mA 0.1mA 0.0~ 104.9mA | ± 2% ± 0.7mA
1000mA 1mA 80~ 1049mA | ± 2% 
10A 0.01A 0.80~ 10.49A
30A 0.1A 8.0~ 31.5A
Operating indication
Earth resistance function: 
Constant voltage injection
Current detection ( Frequency: Approx. 2400Hz) 
Dual Integration
AC current function: Successive approximation
Over-range indication " OL " is displayed when input exceeds the upper limit of a measuring range
Response time Approx. 7 seconds ( Earth resistance) 
Approx. 2 seconds ( AC current) 
Sample rate Approx. 1 time per second
Power source LR6/ R6 ( AA) ( 1.5V) × 4
Current consumption Approx. 90mA ( max. 140mA) 
Measurement time Approx. 21 hours ( when LR6 is used) 
Approx. 5 hours ( when R6 is used) 
Auto power-off Turns power off about 10 minutes after the last button operation
Applicable standards IEC 61010-1 CAT.IV 300V Pollution degree 2
IEC 61010-2-032, IEC 61326-2-2 ( EMC) 
Withstand voltage AC 5320Vrms/ 5 seconds
Between the Transformer jaws fitted parts and case enclosure ( except for jaws) 
Conductor size Approx. Æ 32mm
Dimension 246 ( L) × 120 ( W) × 54 ( D) mm
Weight Approx. 780g ( including batteries) 
Accessories 8304 ( Resistors for operation check) 
9167 ( Carrying case [ Hard] ) 
LR6 ( AA) × 4, Instruction manual

Permintaan Penawaran